How to calculate the power supply and power consumption budget during the peak hours of the hotel

单品功耗基线

  • 售货机(制冷)峰值 320W,均值 120W
  • 充电终端待机 3W,满载 45W
  • 联控主机 15W

同时系数

高峰时段按 0.6 同时系数估算,避免按峰值简单相加导致容量浪费。

线路与空开

单回路建议不超过 16A,多台设备分回路供电,空调与大功率设备独立回路。

压降校核

末端线路超过 30 米时校核压降,超过 5% 需加粗线径。

现场实测比计算更重要,建议用钳形表在高峰时段复核。